Properties
The IKI-20 is suitable for the detection, indication and remote signalling of short circuits in power distribution networks. In addition, in power distribution networks with rigidly, low-resistance or short-time low-resistance grounded neutral point, the detection, indication and remote signalling of ground short-circuits is possible. Non-directional earth faults can be indicated in cleared or isolated networks.The IKI-20 is maintenance-free because the power supply is provided by the current transformers.
Measurement functions and display
- Reliable measured value processing through independent overcurrent-time characteristic (UMZ measurement function)
- True current measurement
- Self-explanatory LCD-. symbols
- additional very bright LED flashing display
Universal setting option of operating parameters
- response current and response time separately for short circuit and earth short circuit
- reset mode resp. reset time
- Relay functions duration or wiping contact
Self test
- Function test on site by means of test button or remotely controllable via auxiliary input
Operation in ring and beam network (without switching)
- Differentiated display of first and second fault event in networks with AWE
Variants
Buffering of power supply
-
IKI-20T:
Buffering of power supply via low voltage (110 … 230 VAC); additional capacitor buffering for at least 12 h
-
IK-20U:
Buffering of power supply via wide range auxiliary voltage input 24 … 230 VAC/DC, capacitor buffering
-
IK-20B:
Buffering of power supply via integrated lithium battery (lifetime >17 years with current transformers not connected)
Relay outputs as floating transient or permanent contacts
-
IKI-20X1:
1 relay with 1 NO contact and 1 NC contact for all faults
-
IKI-20X2:
2 relays with 1 NC contact or 1 NO contact for short-circuit and 1 NC contact or 1 NO contact for ground fault
-
IKI-20X3
3 relays with 1 NC contact or 1 NO contact with common root for phase-selective faults at L1, L2, L3